CONFIRMATORY SAMPLING PROTOCOL |
|||||
|
SOIL UNDER TANK ACCESSIBLE - NO WATER ENCOUNTERED |
|||||
|
|
TANKS* |
PRODUCT DISPENSERS |
DELIVERY LINES |
REMOTE FILL (IF PRESENT) |
|
|
|
|
|
|||
|
SOIL |
2 |
3 |
1 |
1** |
1 |
|
COMMENTS |
Take Samples 2 Ft. Below Bottom of Tank-See Closure Guidance For Specific Locations |
Take 1 Sample Per Dispenser, 2 Ft. Below Surface Directly Under Dispenser |
Take 1 Ft. Below Line |
Take 2 Ft. Below Fill Opening |
|
|
SOIL UNDER TANK ACCESSIBLE - WATER ENCOUNTERED WITHIN 2 FEET OF TANK BOTTOM |
|||||
|
|
TANKS* |
PRODUCT DISPENSER |
DELIVERY LINES |
REMOTE FILL (IF PRESENT) |
|
|
|
|
|
|||
|
SOIL |
2 |
3 |
1 |
1** |
1 |
|
WATER |
2 |
3 |
*** |
*** |
*** |
|
COMMENTS |
One Soil Sample And One Water Sample Just Above Soil/Water Interface- See Closure Guidance for Specific Locations |
Take 1 Sample Per Dispenser, 2 Ft. Below Surface Directly Under Dispenser |
Take 1 Ft. Below Line |
Take 2 Ft. Below Fill Opening |
|
|
SOIL UNDER TANK NOT ACCESSIBLE OR WATER ENCOUNTERED BETWEEN TANK BOTTOM AND GROUND SURFACE (Using Perimeter Borings) |
|||||
|
|
TANKS* |
PRODUCT DISPENSER |
DELIVERY LINES |
REMOTE FILL (IF PRESENT) |
|
|
|
<3000 GAL |
3001-20000 gal |
|||
|
SOIL |
4 |
6 |
1 |
1** |
1 |
|
WATER |
4 |
6 |
*** |
*** |
*** |
|
COMMENTS |
One Soil Sample And One Water Sample (If Water Encountered) Per Boring Just Above Soil/Water Interface- See Closure Guidance for Specific Locations |
Take 1 Sample Per Dispenser, 2 Ft. Below Surface Directly Under Dispenser |
Take 1 Ft. Below Line |
Take 2 Ft. Below Fill Opening |
|
| * For tanks in excess of 20,000 gallons, contact the DEP Regional Office responsible
for the county in which the tank is located. ** If piping is also closed-in-place, see Section VI.C.2.e.(2), pg. 22. *** Assumes water is not encountered. |
|||||