CONFIRMATORY SAMPLING PROTOCOL TANK REMOVAL Number of Samples |
|||||
|
NO WATER ENCOUNTERED |
|||||
|
|
TANKS* |
PRODUCT |
DELIVERY |
REMOTE FILL |
|
|
|
|
|
DISPENSERS |
LINES |
(IF PRESENT) |
|
SOIL** |
2 |
3 |
1 |
1*** |
1 |
|
|
Take Samples 2 Ft. Below Bottom of Tank-See Closure Guidance For Specific Locations |
Take 1 Sample Per Dispenser, 2 Ft. Below Surface Directly Under Dispenser |
Take 1 Ft. Below Line |
Take 2 Ft. Below Fill Opening |
|
|
WATER ENCOUNTERED |
|||||
|
|
TANKS* |
PRODUCT |
DELIVERY |
REMOTE FILL |
|
|
|
|
|
DISPENSERS |
LINES |
(IF PRESENT) |
|
SOIL** |
2 |
2 |
1 |
1*** |
1 |
|
WATER |
1 |
2 |
**** |
**** |
**** |
|
COMMENTS |
Take Soil Samples Just Above Soil/Water Interface Along Each Long Wall Of Excavation-Take Water Samples From Excavation |
Take 1 Sample Per Dispenser, 2 Ft. Below Surface Directly Under Dispenser |
Take 1 Ft. Below Line |
Take 2 Ft. Below Fill Opening |
|
|
*	For tanks in excess of 20,000 gallons, contact the DEP Regional Office responsible for the county in which the tank is located. **	Where obvious contamination is observed, one composite sample per 100 cubic yards of the uncontaminated soil pile must be collected at a minimum depth of 12 inches, if it is intended to be reused on-site. Also, for up to 100 cubic yards, one discrete sample for each 50 cubic yards or fraction thereof, of the contaminated soil pile must be collected, if it is intended to be reused on-site. One discrete sample for each additional 100 cubic yards of contaminated soil must also be taken. The samples are to be taken from the most obviously contaminated areas based upon visual observation and field screening. ***	If piping is closed-in-place, see Section VI.C.2.e.(2), p. 22. ****	Assumes water is not encountered. |
|||||